About TKK
Industrial Goods
Solutions
Quotation
Shop Industrial Products
News
Work with us
Thank you! Your submission has been received!
Oops! Something went wrong while submitting the form.
Contact Us

APISTE Pump, Blower & Vacuum Systems Panel Cooling Unit – Outdoor Lateral-mount Type

Panel Cooling Unit – Outdoor Lateral-mount Type

Panel Cooling Unit – Outdoor Lateral-mount Type

APISTE Panel Cooling Unit – Outdoor Lateral-mount […]
สนใจสินค้า
Type
Model :
Panel Cooling Unit – Outdoor Lateral-mount Type
Screw diameter for both ends:
Applicable fluid:
Features

APISTE Panel Cooling Unit –Outdoor Lateral-mount Type

ENC-A510HD/A520HD

ENC-AR510HD/AR520HD

ENC-A1010HD/A1020HD

ENC-AR1010HD/AR1020HD

ENC-A1610HD/A1620HD

ENC-AR1610HD/AR1620HD

ENC-A2900HD

ENC-AR2900HD

ENC-A510HD/A520HD

ENC-A510HD

ENC-A520HD

ENC-AR510HD/AR520HD

ENC-AR510HD

ENC-AR520HD

ENC-A1010HD/A1020HD

ENC-A1010HD

ENC-A1020HD

ENC-AR1010HD/AR1020HD

ENC-AR1010HD

ENC-AR1020HD

ENC-A1610HD/A1620HD

ENC-A1610HD

ENC-A1620HD

ENC-AR1610HD/AR1620HD

ENC-AR1610HD

ENC-AR1620HD

ENC-A2900HD

ENC-A2900HD

ENC-AR2900HD

ENC-AR2900HD

Model

ENC-A510HD

ENC-A520HD

Type

Outdoors lateral-mount type

Cooling scheme

Compressor

Cooling capacity (W)

300/380(50/60Hz)

Power supply (50/60Hz)

1 phase 100VAC±10%

1 phase 200VAC±10%

Current consumption (A)(MAX)

3.9/3.8

2.0/1.7

Starting current (A)

7.4/7.7

4.0/4.2

Power consumption (W)(MAX)

330/370

330/320

Allowable ambient temperature (ºC)

0 to 50

Allowable ambient humidity (%)

10 to 85 (No condensation)

Operation control scheme

Microcomputer-based automatic control

Refrigerant

R-134a (A kind of freon that is not prohibited)

Temperature setting range (ºC)

25 to 45

Number of fans

1

Outer dimensions (mm)

H:300×W:115×D:530

Weight(kg)

15

Model

ENC-AR510HD

ENC-AR520HD

Type

Outdoors lateral-mount type

Cooling scheme

Compressor

Cooling capacity (W)

450/550(50/60Hz)

Power supply (50/60Hz)

1 phase 100VAC±10%

1 phase 200VAC±10%

Current consumption (A)(MAX)

3.9/4.2

2.1/1.9

Starting current (A)

7.4/7.7

4.9/4.4

Power consumption (W)(MAX)

365/410

365/360

Allowable ambient temperature (ºC)

-5 to 50

Allowable ambient humidity (%)

10 to 85 (No condensation)

Operation control scheme

Microcomputer-based automatic control

Refrigerant

R-134a (A kind of freon that is not prohibited)

Temperature setting range (ºC)

25 to 45

Number of fans

2

Outer dimensions (mm)

H:450×W:350×D:200

Weight(kg)

17

Model

ENC-A1010HD

ENC-A1020HD

Type

Outdoors lateral-mount type

Cooling scheme

Compressor

Cooling capacity (W)

900/1000 (50/60Hz)

Power supply (50/60Hz)

1 phase 100VAC±10%

1 phase 200VAC±10%

Current consumption (A)(MAX)

6.5/6.3

3.1/3.0

Starting current (A)

15.6/14.7

7.5/7.1

Power consumption (W)(MAX)

595/615

570/590

Allowable ambient temperature (ºC)

-5 to 50

Allowable ambient humidity (%)

10 to 85 (No condensation)

Operation control scheme

Microcomputer-based automatic control

Refrigerant

R-134a

Temperature setting range (ºC)

25 to 45

Number of fans

2

Output

Output of operation & alarm(250V 2A)

Display

LED Temperature/Error Run

Noise immunity

Level 4 in the fast transient/Burst immunity test

Noise (dB)

Approx. 64/66

Vibration resistance

Vibration frequency : 5Hz ; a double amplitude of 20mm

Outer dimensions (mm)

H730×W300×D280

Weight(kg)

26

Model

ENC-AR1010HD

ENC-AR1020HD

Type

Outdoors lateral-mount type

Cooling scheme

Compressor

Cooling capacity (W)

900/1000 (50/60Hz)

Power supply (50/60Hz)

1 phase 100VAC±10%

1 phase 200VAC±10%

Current consumption (A)(MAX)

6.5/6.3

3.1/3.0

Starting current (A)

15.6/14.7

7.5/7.1

Power consumption (W)(MAX)

595/615

570/590

Allowable ambient temperature (ºC)

-5 to 50

Allowable ambient humidity (%)

10 to 85 (No condensation)

Operation control scheme

Microcomputer-based automatic control

Refrigerant

R-134a

Temperature setting range (ºC)

25 to 45

Number of fans

2

Output

Output of operation & alarm(250V 2A)

Display

LED Temperature/Error Run

Noise immunity

Level 4 in the fast transient/Burst immunity test

Noise (dB)

Approx. 64/66

Vibration resistance

Vibration frequency : 5Hz ; a double amplitude of 20mm

Outer dimensions (mm)

H730×W300×D280

Weight(kg)

26

Model

ENC-A1610HD

ENC-A1620HD

Type

Outdoors lateral-mount type

Cooling scheme

Compressor

Cooling capacity (W)

1450/1600 (50/60Hz)

Power supply (50/60Hz)

1 phase 100VAC±10%

1 phase 200VAC±10%

Current consumption (A)(MAX)

8.5/8.8

4.3/4.5

Starting current (A)

22.3/20.5

13/12

Power consumption (W)(MAX)

740/830

780/840

Allowable ambient temperature (ºC)

-5 to 50

Allowable ambient humidity (%)

10 to 85 (No condensation)

Operation control scheme

Microcomputer-based automatic control

Refrigerant

R-407c (A kind of freon that is not prohibited)

Temperature setting range (ºC)

25 to 45

Number of fans

4

Outer dimensions (mm)

H:1000×W:400×D:260

Weight(kg)

42

Model

ENC-AR1610HD

ENC-AR1620HD

Type

Outdoors lateral-mount type

Cooling scheme

Compressor

Cooling capacity (W)

1450/1600 (50/60Hz)

Power supply (50/60Hz)

1 phase 100VAC±10%

1 phase 200VAC±10%

Current consumption (A)(MAX)

8.5/8.8

4.3/4.5

Starting current (A)

22.3/20.5

13/12

Power consumption (W)(MAX)

740/830

780/840

Allowable ambient temperature (ºC)

-5 to 55

Allowable ambient humidity (%)

10 to 85 (No condensation)

Operation control scheme

Microcomputer-based automatic control

Refrigerant

R-407c (A kind of freon that is not prohibited)

Temperature setting range (ºC)

25 to 45

Number of fans

4

Outer dimensions (mm)

H:1000×W:400×D:260

Weight(kg)

42

Model

ENC-A2900HD

Type

Outdoors lateral-mount type

Cooling scheme

Compressor

Cooling capacity (W)

2600/2900(50/60Hz)

Power supply (50/60Hz)

1 phase 200VAC±10%

Current consumption (A)(MAX)

9.3/9.4

Starting current (A)

33/30

Power consumption (W)(MAX)

1650/1850

Allowable ambient temperature (ºC)

-5 to 55

Allowable ambient humidity (%)

10 to 85 (No condensation)

Operation control scheme

Microcomputer-based automatic contorl

Refrigerant

R-134a (A kind of freon that is not prohibited)

Temperature setting range (ºC)

25 to 45

Number of fans

6

Outer dimensions (mm)

H:1380×W:450×D:295

Weight(kg)

60

Model

ENC-AR2900HD

Type

Outdoors lateral-mount type

Cooling scheme

Compressor

Cooling capacity (W)

2600/2900(50/60Hz)

Power supply (50/60Hz)

1 phase 200VAC±10%

Current consumption (A)(MAX)

9.3/9.4

Starting current (A)

33/30

Power consumption (W)(MAX)

1650/1850

Allowable ambient temperature (ºC)

-5 to 55

Allowable ambient humidity (%)

10 to 85 (No condensation)

Operation control scheme

Microcomputer-based automatic contorl

Refrigerant

R-134a (A kind of freon that is not prohibited)

Temperature setting range (ºC)

25 to 45

Number of fans

6

Outer dimensions (mm)

H:1380×W:450×D:295

Weight(kg)

60