About TKK
Industrial Goods
Solutions
Quotation
Shop Industrial Products
News
Work with us
Thank you! Your submission has been received!
Oops! Something went wrong while submitting the form.
Contact Us

APISTE Pump, Blower & Vacuum Systems Panel Cooling Unit – Non-drain Lateral-mount Type

Panel Cooling Unit – Non-drain Lateral-mount Type

Panel Cooling Unit – Non-drain Lateral-mount Type

APISTE Panel Cooling Unit – Non-drain Lateral-mou […]
สนใจสินค้า
Type
Model :
Panel Cooling Unit – Non-drain Lateral-mount Type
Screw diameter for both ends:
Applicable fluid:
Features

APISTE Panel Cooling Unit –Non-drain Lateral-mount Type

ENC-AR310LE/AR320LE

ENC-AR510LE/AR520LE

ENC-AR810LE/AR820LE

ENC-AR1310LE

ENC-AR1320LE

ENC-AR2400LE

ENC-AR310LE/AR320LE

ENC-AR310LE

ENC-AR320LE

ENC-AR510LE/AR520LE

ENC-AR510LE

ENC-AR520LE

ENC-AR810LE/AR820LE

ENC-AR810LE

ENC-AR820LE

ENC-AR1310LE

ENC-AR1310LE

ENC-AR1320LE

ENC-AR1320LE

ENC-AR2400LE

ENC-AR2400LE

Model

ENC-AR310LE

ENC-AR320LE

Type

Non-drain Lateral-mount type

Cooling scheme

Compressor

Cooling capacity (W)

280/300 (50/60Hz)

Power supply (50/60Hz)

1 phase 100VAC±10%

1 phase 200VAC±10%

Current consumption (A)(MAX)

3.7/3.8

2.1/1.9

Starting current (A)

7.4/7.7

4.0/4.2

Power consumption (W)(MAX)

340/370

360/355

Allowable ambient temperature (ºC)

20 to 50

Allowable ambient humidity (%)

10 to 85 (No condensation)

Refrigerant

R-134a (A kind of freon that is not prohibited)

Temperature setting range (ºC)

25 to 45

Number of fans

2

Output

Output of operation & alarm(250V 2A)

Display

LED Temperature/Error RUN

Noise immunity

Level 4 in the fast transient/Burst immunity test

Noise (dB)

Approx. 59/63

Vibration resistance

Vibration frequency : 5Hz ; a double amplitude of 20mm

Paint color

Munsell 5Y7/1 Equivalent color of light beige

Outer dimensions (mm)

H590×W200×D250

Weight(kg)

18

Model

ENC-AR510LE

ENC-AR520LE

Type

Non-drain Lateral-mount type

Cooling scheme

Compressor

Cooling capacity (W)

400/500 (50/60Hz)

Power supply (50/60Hz)

1 phase 100VAC±10%

1 phase 200VAC±10%

Current consumption (A)(MAX)

3.6/3.7

1.9/1.6

Starting current (A)

7.4/7.7

4.0/4.2

Power consumption (W)(MAX)

320/360

330/300

Allowable ambient temperature (ºC)

20 to 50

Allowable ambient humidity (%)

10 to 85 (No condensation)

Refrigerant

R-134a (A kind of freon that is not prohibited)

Temperature setting range (ºC)

25 to 45

Number of fans

2

Output

Output of operation & alarm(250V 2A)

Display

LED Temperature/Error RUN

Noise immunity

Level 4 in the fast transient/Burst immunity test

Noise (dB)

Approx. 63/67

Vibration resistance

Vibration frequency : 5Hz ; a double amplitude of 20mm

Paint color

Munsell 5Y7/1 Equivalent color of light beige

Outer dimensions (mm)

H500×W350×D230

Weight(kg)

19

Model

ENC-AR810LE

ENC-AR820LE

Type

Non-drain Lateral-mount type

Cooling scheme

Compressor

Cooling capacity (W)

700/800 (50/60Hz)

Power supply (50/60Hz)

1 phase 100VAC±10%

1 phase 200VAC±10%

Current consumption (A)(MAX)

6.5/6.4

3.2/3.2

Starting current (A)

15.6/14.7

7.5/7.1

Power consumption (W)(MAX)

590/630

600/610

Allowable ambient temperature (ºC)

20 to 50

Allowable ambient humidity (%)

10 to 85 (No condensation)

Refrigerant

R-134a (A kind of freon that is not prohibited)

Temperature setting range (ºC)

25 to 45

Number of fans

2

Output

Output of operation & alarm(250V 2A)

Display

LED Temperature/Error RUN

Noise immunity

Level 4 in the fast transient/Burst immunity test

Noise (dB)

Approx. 64/68

Vibration resistance

Vibration frequency : 5Hz ; a double amplitude of 20mm

Paint color

Munsell 5Y7/1 Equivalent color of light beige

Outer dimensions (mm)

H730×W300×D280

Weight(kg)

26

Model

ENC-AR1310LE

Type

Non-drain Lateral-mount Type

Cooling scheme

Compressor

Cooling capacity (W)

1150/1300(50/60Hz)

Power supply (50/60Hz)

1 phase 100VAC±10%

Current consumption (A)(MAX)

8.6/9.0

Starting current (A)

22.3/20.5

Power consumption (W)(MAX)

770/870

Allowable ambient temperature (ºC)

20 to 55

Allowable ambient humidity (%)

10 to 85 (No condensation)

Refrigerant

R-407c

Temperature setting range (ºC)

25 to 45

Number of fans

3

Output

Output of operation & alarm(250V 2A)

Display

LED Temperature/Error RUN

Noise immunity

Level 4 in the fast transient/Burst immunity test

Noise (dB)

Approx. 68/72

Vibration resistance

Vibration frequency : 5Hz ; a double amplitude of 20mm

Paint color

Munsell 5Y7/1 Equivalent color of light beige

Outer dimensions (mm)

H900×W400×D251

Weight(kg)

36

Model

ENC-AR1320LE

Type

Non-drain Lateral-mount Type

Cooling scheme

Compressor

Cooling capacity (W)

1150/1300 (50/60Hz)

Power supply (50/60Hz)

1 phase 200V±10%

Current consumption (A)(MAX)

4.2/4.4

Starting current (A)

12.7/11.6

Power consumption (W)(MAX)

805/880

Allowable ambient temperature (ºC)

20 to 50

Allowable ambient humidity (%)

10 to 85 (No condensation)

Refrigerant

R-407c

Temperature setting range (ºC)

25 to 45

Number of fans

3

Output

Output of operation & alarm(250V 2A)

Display

LED Temperature/Error RUN

Paint color

Munsell 5Y7/1 Equivalent color of light beige

Outer dimensions (mm)

H900×W400×D251

Weight(kg)

36

Model

ENC-AR2400LE

Type

Non-drain Lateral-mount Type

Cooling scheme

Compressor

Cooling capacity (W)

2100/2400(50/60Hz)

Power supply (50/60Hz)

3 phase 200VAC±10%

Current consumption (A)(MAX)

5.0/4.6

Starting current (A)

31/30

Power consumption (W)(MAX)

1490/1770

Allowable ambient temperature (ºC)

20 to 55

Allowable ambient humidity (%)

10 to 85 (No condensation)

Refrigerant

R-134a

Temperature setting range (ºC)

25 to 45

Number of fans

5

Output

Output of operation & alarm(250V 2A)

Display

LED Temperature/Error RUN

Noise immunity

Level 4 in the fast transient/Burst immunity test

Noise (dB)

Approx. 70/73

Vibration resistance

Vibration frequency : 5Hz ; a double amplitude of 20mm

Paint color

Munsell 5Y7/1 Equivalent color of light beige

Outer dimensions (mm)

H1380×W450×D230

Weight(kg)

63

Application